RTV coating for substation
RTV covering presented as an effective and economic maintenance method. In addition, this method compares with. HVIC is the only appropriate method for high NSDD and “very heavy” pollution degree regions and recommended.
Supplier information
Namdar Sanat Azar Asa
Iran (Islamic Republic of), TehranManufacturer, Importer, Exporter, Service provider
Multi Chamber arrester, RTV coating
View supplier websiteخرید از تامین کنندگان برتر پارس سنتر!
تامین کنندگان برتر پارس سنتر سرعت پاسخگویی بالاتر و محصولات بروز تری نسبت به سایر تامین کنندگان دارند.
Service description
High voltage insulators have to be used as insulating supporters in various environments in polluted area. The electrical performance of insulators will be degraded. The polluted insulators will have over withstand voltage, flashover can occur easily when the air becomes wet by humidity or fog, which affects on the reliability of the power systems. In order to define effective counter measures against pollution flashovers there are conventional methods such as periodically water washing and also using silicone grease for insulation. Water washing of insulators which is normally recommended so as to remove the pollution from the insulator surface needs to be done more frequently than other maintenance methods. Though involves some limitation in practice from the technical and economical point of view. Applying of silicon grease on insulators with high cost of performance also is not recommended for use in an environment where high level of NSDD pollution is present. In this paper room temperature vulcanizing (RTV) silicone rubber coating have been presented as a novel approach for improvement of outdoor substation insulators maintenance in polluted area. This method can be used in areas characterized with “Instantaneous pollution” and or with “High or Low level of NSDD” with long life expectancy. Financial analysis shows that this method is also economic and optimal choice.